MESINA Products MESINA Atmospheric Cooling Tower
Advantages of Atmospheric Cooling Towers :
  • For Power Plants
  • For Chemical Plants
  • For Cooling Process Hot Water
  • For Air Cooling Plants
  • No Electrical Connection
  • No Fan Motor
  • No Cabling
Title Detail
LOUVRES : Galvanised Iron / PVC.
SPRAY PIPES : Made from class ‘ B ’ GI pipes with removable nozzles.
FRAME WORK : Constructed from zinc coated MS angle 40 x 40 x 5mm for model upto 4; 50 x 50 x 5 mm for models 5 to 9.GI bolts and nuts.
TANK : Constructed from 3 mm plates with water angle stifners and inlet, outlet, drain makeup water socket connections.2 coats of red oxide and zinc chromite corrosion resists paints.
STRAINER : Brass water strainer removable in tank at the water outlet.
Water On : 36.3°C
Water Off : 32.2°C
Ambient Temp : 27°C
Tank Depth : 300mm
Model
No.
T.R Size G P M L P M Pipe
In/Out
Conn in
(mm)NB
Wt. Kg Recommended
Condensor
Pump HP
CT0750 7.5 1250 x 1250 x 2100 31 142 40 380 2
CT1000 10 1250 x 1875 x 2400 41 185 40 430 2
CT1500 15 1250 x 2500 x 2400 61 278 40 510 3
CT2000 20 1250 x 2500 x2700 82 370 65 550 3
CT2500 25 1875 x 2500 x 2700 102 464 80 550 5
CT3000 30 2500 x 2500 x 3000 123 556 80 650 7.5
CT4000 40 2500 x 3000 x 3300 153 695 100 750 7.5
CT4500 45 2500 x 3000 x 3650 163 741 100 970 7.5
CT5000 50 2750 x 3000 x 3650 204 926 100 1100 7.5

Continuous research results in steady improvements. Therefore, these specifications are subject to change without notice.