Advantages of Atmospheric Cooling Towers :
-
For Power Plants
- For Chemical Plants
- For Cooling Process Hot Water
- For Air Cooling Plants
- No Electrical Connection
- No Fan Motor
- No Cabling
Title
|
Detail
|
LOUVRES :
|
Galvanised Iron / PVC.
|
SPRAY PIPES :
|
Made from class ‘ B ’ GI pipes with removable nozzles.
|
FRAME WORK :
|
Constructed from zinc coated MS angle 40 x 40 x 5mm for model upto 4; 50 x 50 x 5 mm for models 5 to 9.GI bolts and nuts.
|
TANK :
|
Constructed from 3 mm plates with water angle stifners and inlet, outlet, drain makeup water socket connections.2 coats of red oxide and zinc chromite corrosion resists paints.
|
STRAINER :
|
Brass water strainer removable in tank at the water outlet.
|
Water On :
|
36.3°C
|
Water Off :
|
32.2°C
|
Ambient Temp :
|
27°C
|
Tank Depth :
|
300mm
|
Model No.
|
T.R
|
Size
|
G P M
|
L P M
|
Pipe
In/Out
Conn in
(mm)NB
|
Wt. Kg
|
Recommended Condensor Pump HP
|
CT0750
|
7.5
|
1250 x 1250 x 2100
|
31
|
142
|
40
|
380
|
2
|
CT1000
|
10
|
1250 x 1875 x 2400
|
41
|
185
|
40
|
430
|
2
|
CT1500
|
15
|
1250 x 2500 x 2400
|
61
|
278
|
40
|
510
|
3
|
CT2000
|
20
|
1250 x 2500 x2700
|
82
|
370
|
65
|
550
|
3
|
CT2500
|
25
|
1875 x 2500 x 2700
|
102
|
464
|
80
|
550
|
5
|
CT3000
|
30
|
2500 x 2500 x 3000
|
123
|
556
|
80
|
650
|
7.5
|
CT4000
|
40
|
2500 x 3000 x 3300
|
153
|
695
|
100
|
750
|
7.5
|
CT4500
|
45
|
2500 x 3000 x 3650
|
163
|
741
|
100
|
970
|
7.5
|
CT5000
|
50
|
2750 x 3000 x 3650
|
204
|
926
|
100
|
1100
|
7.5
|
Continuous research results in steady improvements. Therefore, these specifications are subject to change without notice.
|